How to make the print_char work in character mode on both ports of BMXNOM0200?

1.Issue

Once customer enables the print_char block to one port of BMXNOM0200 with character mode(without connection on this port),  the print_char on the other port will stop working after 30sec.

2.Environment

Issue only happens when NOM is on the  BMxCRA312xx drop.

3.Resolution

Set the ‘Immediate acknowledge bit’  of GEST variable to TRUE. Then, the NOM module will immediately answer to the input character request even if no character is available so that it will release the communication resources in time.(attached snapshot)

4.FAQ Applicable Conditions

FAQ also applies to input_byte or input_char when using character mode on both ports & one port
experiences communication time out.

Schneider Electric Suomi

Liitteet
NOMmode.png [15.05 KB]
Lue lisää
Tuotesarja:
Lue lisää
Tuotesarja:

Tarvitsetko apua?

  • Tuotevalitsin

    Valitse tarpeitasi vastaavat tuotteet ja lisävarusteet nopeasti ja helposti.

  • Pyydä tarjous

    Ota yhteyttä myyntilomakkeen kautta. Asiantuntijamme ovat sinuun yhteydessä.

  • Löydä lähin jälleenmyyjä

    Löydä helposti lähin jälleenmyyjä.

  • Asiakaspalvelukeskus

    Löydä tukiresurssit kaikkiin tarpeisiisi yhdestä paikasta.

  • Tuotedokumentaatio
  • Ohjelmistolataukset
  • Tuotevalitsin
  • Tuotteen korvaaminen ja vaihtaminen
  • Asiakaspalvelukeskus
  • Etsi toimistomme
  • Pyydä tarjous
  • Osta täältä
  • Shop.se.com/fi/fi sulkeutuu
  • Uramahdollisuudet
  • Yritys
  • Ilmoita väärinkäytöksestä
  • Saavutettavuus
  • Newsroom
  • Sijoittajat
  • Tutustu EcoStruxure
  • Toimipisteet Suomessa
  • Löydä jälleenmyyjä
  • Avoimet työpaikat
  • Blogi
  • Tietosuojakäytäntö
  • Evästeilmoitus
  • Käyttöehdot
  • Muokkaa evästeasetuksia