Product Line
Power Monitoring Expert 9.0
Environment
DTE - Device Type Editor
Issue
The new devices created with DTE are not loading and you will see error messages in the System Log:
"Translator map file 'DEVICE_NAME.xml' not loaded due to previous error. Will retry."
"The attribute 'TimestampedByPlugin' on this element is not defined in the DTD/Schema." - (or some other attribute as well)
Cause
The modbus-schema.xml file in the config/translator folder is an old version and does not contain the specific attribute referred by the error log.
Resolution
Replace the modbus-schema.xml file in config/translator with the one from system/translator folder or from a healthy PME system.
Power Monitoring Expert 9.0
Environment
DTE - Device Type Editor
Issue
The new devices created with DTE are not loading and you will see error messages in the System Log:
"Translator map file 'DEVICE_NAME.xml' not loaded due to previous error. Will retry."
"The attribute 'TimestampedByPlugin' on this element is not defined in the DTD/Schema." - (or some other attribute as well)
Cause
The modbus-schema.xml file in the config/translator folder is an old version and does not contain the specific attribute referred by the error log.
Resolution
Replace the modbus-schema.xml file in config/translator with the one from system/translator folder or from a healthy PME system.
Julkaistu: Schneider Electric Suomi


Tarvitsetko apua?
Tuotevalitsin
Valitse tarpeitasi vastaavat tuotteet ja lisävarusteet nopeasti ja helposti.
Pyydä tarjous
Ota yhteyttä myyntilomakkeen kautta. Asiantuntijamme ovat sinuun yhteydessä.
Löydä lähin jälleenmyyjä
Löydä helposti lähin jälleenmyyjä.
Asiakaspalvelukeskus
Löydä tukiresurssit kaikkiin tarpeisiisi yhdestä paikasta.