Can a logic input be assigned to the external fault in ATV320 drive?
Issue:
How can I configure an external fault using logic input in ATV320 drive?
Product Line:
ATV320 drive
Environment:
All Serial numbers
Cause:
Application requires an external fault via a logic input.
Resolution:
Yes, a logic input can be assigned to a external fault.
External Fault can be accessed: DRI- > CONF > FULL > FLT- > EtF- > EtF
Then assign (LI1) to (LI6), logic input that is not assigned to any other functions.
Logic can be configured (LEt) As LO [Active low] (LO) or HIG [Active high] (HIG)(default).
It defines the positive or negative logic of the input assigned to the detected fault.
Configure EPL [External fault mgt] for Type of stop in the event of an external fault.
How can I configure an external fault using logic input in ATV320 drive?
Product Line:
ATV320 drive
Environment:
All Serial numbers
Cause:
Application requires an external fault via a logic input.
Resolution:
Yes, a logic input can be assigned to a external fault.
External Fault can be accessed: DRI- > CONF > FULL > FLT- > EtF- > EtF
Then assign (LI1) to (LI6), logic input that is not assigned to any other functions.
Logic can be configured (LEt) As LO [Active low] (LO) or HIG [Active high] (HIG)(default).
It defines the positive or negative logic of the input assigned to the detected fault.
Configure EPL [External fault mgt] for Type of stop in the event of an external fault.
Julkaistu: Schneider Electric Suomi


Tarvitsetko apua?
Tuotevalitsin
Valitse tarpeitasi vastaavat tuotteet ja lisävarusteet nopeasti ja helposti.
Pyydä tarjous
Ota yhteyttä myyntilomakkeen kautta. Asiantuntijamme ovat sinuun yhteydessä.
Löydä lähin jälleenmyyjä
Löydä helposti lähin jälleenmyyjä.
Asiakaspalvelukeskus
Löydä tukiresurssit kaikkiin tarpeisiisi yhdestä paikasta.