Kuinka voimme auttaa sinua tänään?

Why Does the Smart-UPS Ultra Battery Cycle Between 94% and 100% State of Charge?

Issue:

The battery state of charge of certain Smart-UPS Ultra models may fluctuate between 94% and 100% during normal operation.

Product Line:

Smart-UPS Ultra 5-10kW

  • Models; SRTL5KRM2UI, SRTL5KRM2UT, SRTL8KRM4UI, SRTL8KRM4UT, SRTL10KRM4UI, SRTL10KRM4UT

Smart-UPS Modular Ultra

  • All models starting with the prefix SRYL

Answer:

This behavior is normal and expected.


The UPS uses a Li-ion battery charging strategy designed to protect battery health. Once the battery reaches 100% state of charge (SoC), the charger is intentionally turned off.


During normal operation, the battery will then discharge slightly. When the SoC drops to approximately 94%, the charger automatically turns back on to recharge the battery.


As a result, the reported battery SoC may cycle between ~94% and 100%. This is part of normal operation and does not indicate a fault or defect.

Schneider Electric Suomi

Lue lisää

Tarvitsetko apua?

Tuotevalitsin

Valitse tarpeitasi vastaavat tuotteet ja lisävarusteet nopeasti ja helposti.

Pyydä tarjous

Ota yhteyttä myyntilomakkeen kautta. Asiantuntijamme ovat sinuun yhteydessä.

Löydä lähin jälleenmyyjä

Löydä helposti lähin jälleenmyyjä.

Asiakaspalvelukeskus

Löydä tukiresurssit kaikkiin tarpeisiisi yhdestä paikasta.