Search FAQs
What are probable causes of SCF1 on Altivar 32 drive.
SCF1 is motor short circuit fault.
Probable cause:
Short-circuit or grounding at the drive output.
Remedy:
Probable cause:
Short-circuit or grounding at the drive output.
Remedy:
- Check the cables connecting the drive to the motor and the motor insulation.
- Reduce the switching frequency.
- Connect chokes in series with the motor.
- Check the adjustment of speed loop.