How to add a Quantum NOM module into the local rack with Concept software.

Issue:
How to add a Quantum NOM module into the local rack with Concept software.


Product Line:
Quantum, Concept


Resolution:
To add a NOM module into the local rack first open the I/O Map and choose "Head Setup".

IO Map

Under NOM in the Head Setup change the Link 1 slot number to the slot number that the NOM will be installed

head setup


Now Go into the Local Drop in the I/O map and the NOM will show up in the Slot number chosen
Local Quantum drop

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.