How many DHCP Address Server entries are supported by the Ethernet modules and Co-Pro's.
Issue
How many DHCP Address Server entries are supported by the Ethernet modules and Co-Pro's.
Product Line
All Premium CoProcessor PLC
All Quantum Co-Processor PLC.
Premium TSXETYxx03 Ethernet modules (TSXETY4103, TSXETY5103).
Quantum 140NOE77xX1 Ethernet modules.
Environment
Windows 10
Resolution
The Unity Quantum Co-Processor PLC supports 128 DHCP Address Server entries.
The Unity Premium Co-Processor PLC supports 128 DHCP Address Server entries.
The Quantum '140NOE771x1' Ethernet module supports 128 DHCP Address Server entries.
The Premium 'TSXETYx103' Ethernet module only supports 96 DHCP Address Server entries.
The Premium 'ETY Port' only supports 96 DHCP Address Server entries