Issue:
Would an I-line panel with 1200 main breaker have GFI protection as standard per NEC
Product Line:
I-Line Panelboards
Environment:
Products sold in North America
Resolution:
It is required by NEC if panel is 277V, 480V or 480V Delta. It is not required if it is 120-208 volts. In any case the ground fault protection would have to be quoted for factory installation. Check with the local Distributor or Sales office for selection and quotation.