Is sprinkler proof bus duct available from Square D by Schneider Electric?
Issue:
Sprinkler proof busway selection

Product Line:
I-Line Busway

Environment:
Products sold in North America

Resolution:
Yes it is available but only with the 800A to 5000A I-Line II series busway product.
IP54 rated busduct will withstand sprinklers. We must density rate the bus bars to receive UL approved product.
IP54 construction is not available for 225 thru 600A busway products.