How to set a start/stop on LI1 and a LSP speed on ATV312 drive?
Use start/stop on LI1 and set a LSP speed on ATV312 drive.
Enter the motor parameters in the DRC menu (BFR: UNS, FRS: NCR: NSP).
Wire a start/stop contact between LI1 and +24V. Set low speed in the SET menu with parameter LSP. Assign the value in frequency.