Issue:
Breaker for I-Line panel
Product Line:
Panelboards
Environment:
I-Line HCP
Cause:
Mounting
Resolution:
Neither the MA or MH breakers will fit in the wide side of this I-Line panel. The cam foot has no where to engage the back panel. Use the HCRU or older HCW interior instead.