How do I troubleshoot an Altivar Process Drive that would not connect to a Ethernet IP network?
Altivar Process Drive connection to Ethernet IP network
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Note: This FAQ goes over some basic checks and troubleshooting tips. For extended troubleshooting please refer to your drives Ethernet IP manual.
Drive Will Not Connect
- Card
- Confirm Card Module is installed. The ATV600 drive (only) has integrated Modbus TCP and not Ethernet IP. Option module card must be used.
- Only works with Firmware V1.5IExx or above for ATV600 drives only. Should work on any ATV900 drive.
- Installation
- Make sure proper Ethernet cable is connected to the appropriate Ethernet serial port.
- Pin Layout - Make sure to use proper pinouts for cables.
- Isolate any electrical interference
- Use conduits or other isolating materials
- Separate control and power connections
- Add terminating resistors if the drive is at the end or the last of device in the network.
- Network
- Check for any duplicate addresses on the network.
- Check to make sure you have proper configured assemblies
- Programming
- Check Basic Settings on the drive. Make sure the following is set:
- IP Assignment Mode
- Set to Fixed
- IP Address
- Subnet Mask
- Gateway Address
- IP Assignment Mode
- Check Basic Settings on the drive. Make sure the following is set:
Drive Connects But Will Not Run
- Network
- Verify you can read from the drive
- Verify reading and writing to correct Modbus registers
- Programming on the Drive
- Confirm drive is setup for Network Control
- Check Command and Reference Menu
- [Complete settings] [Command and Reference]
- Important Note!: For ATV600 drives only, the Ethernet IP option is a Communication Module it is not Embedded. When selecting option for Ethernet IP use the option for "Reference Frequency Via Fieldbus Module" [Com. Module] not [Embedded Ethernet]
- [Complete settings] [Command and Reference]
- Check Command and Reference Menu
- Confirm drive is setup for Network Control
- Troubleshooting
- Check Communication Map
- [Display] [Communication map]
- Check Command Channel
- Command Register
- Ref Freq Channel
- Ref Freq
- [Display] [Communication map]
- Disable FDR settings if not using a Faulty Device Replacement.
- Check LEDs on the drive
- The following FAQ describes the LEDs status for Ethernet IP Field-bus for the Altivar Process Drives
- Check Communication Map
- Reference attached manuals for further troubleshooting
Publicado para: Schneider Electric Mexico




¿Necesitas ayuda?
Selector de productos
Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.
Pedir presupuesto
Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.
Centro de ayuda
Encuentra recursos de soporte para todas tus necesidades en un solo lugar.