How to wire a transformer with a S40F voltage code regardless of the KVA rating?

Issue:
How to connect a transformer with a S40F voltage code regardless of the KVA size?

Product Line:
Resin filled and Epoxy encapsulated transformers

Environment:
Products sold in North America

Resolution:
Connections depend on your application.

Primary:
Apply 480V lines to H1 and H4

Secondary:
For 120/240 Volt 3-wire: Connect X2 and X3 together and bond to ground per the NEC code. 240V outputs are X1 and X4, neutral is the X2/X3 connection

For 120 Volt 2-wire: Connect X2 and X4 together and bond to  ground per the NEC Code. Connect X1 and X3 together. 120V hot line is the X1/ X3 connection, and the neutral is the X2/X4 connection

For 240V connect X2 and X3 together then connect the 240V load wires to X1 and X4.

Schneider Electric Mexico

Explora más
Rango:
Explora más
Rango:

¿Necesitas ayuda?

¿Necesitas ayuda?

Selector de productos

Selector de productos

Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.

Pedir presupuesto

Pedir presupuesto

Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.

¿Dónde comprar?

¿Dónde comprar?

Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.

Centro de ayuda

Centro de ayuda

Encuentra recursos de soporte para todas tus necesidades en un solo lugar.

  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Sustitución y reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Obtén un presupuesto
  • Dónde comprar
  • Comunidad Schneider Electric
  • Empleo
  • Perfil corporativo
  • Informar una conducta indebida
  • Accesibilidad
  • Sala de redacción
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Términos y condiciones
  • Change your cookie settings