What can cause a CANopen CoF fault on the ATV320 drive?
Issue:
ATV320 CANopen CoF fault

Product Line:
Altivar ATV320

Environment:
All

Cause:
Communication interruption on the CANopen® bus.

Resolution:
• Check the CANopen cables on the communication bus, check to see if there are 120 ohm line terminator resistors installed, check and verify baud rate setting parameter BDCO.
• Refer to the CANopen® User's manual: https://www.se.com/ww/en/download/document/NVE41309/

Module LED color & status description
-OFF No detected error reported Red single flash Detected error reported by the CANopen controller of the Altivar 320 (example: too many detected error frames)
-Red double flash Detected error due to the occurrence of a Node Guarding or a Heartbeat event
-Red ON The CANopen controller is in Bus OFF state

Schneider Electric Mexico

Documentos adjuntos
ATV320_CANopen_Manual_EN_NVE41309_02.pdf [1.38 MB]
Explora más
Rango:
Categoría:
Explora más
Rango:
Categoría:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Sustitución y reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Obtén un presupuesto
  • Dónde comprar
  • Comunidad Schneider Electric
  • Empleo
  • Perfil corporativo
  • Informar una conducta indebida
  • Accesibilidad
  • Sala de redacción
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Términos y condiciones
  • Change your cookie settings