Issue:
Which driphood can we use to convert to Nema 3R for a EX45T65H Transformer?
Product Line:
LV Transformer
Environment:
EX
Resolution:
7400WS18K is WeatherShield to convert NEMA1 to NEMA 3R Outdoor. 7400DS18K Drip Shield to convert from NEMA 1 to NEMA 2 drip proof Indoor.
NEMA 2 prevents intrusion of dripping water from above like from a sprinkler head from splashing into the vent and onto the Transformer.