Issue
When using Control Expert / Unity Pro to add either a BMEAHI0812 or BMEAHO0412 in an empty slot it is not allowed.
Product line
Modicon X80, Control Expert, Unity Pro
Resolution
When using the BMEXBP1002, slots 2 and 8 do not support BME******* Ethernet backplane IO modules. Slots 2 and 8 only support BMX******* XBUS backplane IO modules. All of the remaining slots support either BME or BMX modules.
This also applies to the BMEXBP1200 for slots 2,8,10 and 11.
When using Control Expert / Unity Pro to add either a BMEAHI0812 or BMEAHO0412 in an empty slot it is not allowed.
Product line
Modicon X80, Control Expert, Unity Pro
Resolution
When using the BMEXBP1002, slots 2 and 8 do not support BME******* Ethernet backplane IO modules. Slots 2 and 8 only support BMX******* XBUS backplane IO modules. All of the remaining slots support either BME or BMX modules.
This also applies to the BMEXBP1200 for slots 2,8,10 and 11.