What causes an input phase loss PHF fault on the ATV12?

Issue:
Getting a input phase loss PHF fault on ATV12

Product Line:
Altivar Machine, ATV12

Environment:
All serial numbers


Cause:
• Drive incorrectly supplied or a fuse blown
• Failure of one phase
• 3-phase ATV12 used on a 1-phase line supply
• Unbalanced load
• This protection only operates with the drive on load

Resolution:

• Check the power connection and the fuses.
• Use a 3-phase line supply.
• Disable the fault by setting Input Phase loss detection IPL page 94 = nO.
• Check the motor connection and any isolating devices located between the drive and the motor (contactors, circuit breakers, etc.).


ATV12 user manual:
https://www.se.com/ww/en/download/document/BBV28581/

Schneider Electric Mexico

Documentos adjuntos
ATV12_user_manual_EN_BBV28581_04.pdf [3.62 MB]
Explora más
Rango:
Explora más
Rango:

¿Necesitas ayuda?

¿Necesitas ayuda?

Selector de productos

Selector de productos

Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.

Pedir presupuesto

Pedir presupuesto

Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.

¿Dónde comprar?

¿Dónde comprar?

Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.

Centro de ayuda

Centro de ayuda

Encuentra recursos de soporte para todas tus necesidades en un solo lugar.

  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Sustitución y reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Obtén un presupuesto
  • Dónde comprar
  • Comunidad Schneider Electric
  • Empleo
  • Perfil corporativo
  • Informar una conducta indebida
  • Accesibilidad
  • Sala de redacción
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Términos y condiciones
  • Change your cookie settings