Are the K13 rated transformers classified as "Harmonic Mitigating with 0-degree phase shift"
Product Line:
K-rated Energy Efficient Transformers
Environment:
Low Voltage Transformers
Cause:
Clarification on K13 transformers in relation to Harmonic Mitigating application.
Resolution:
No, the K13 transformers are 30 degree phase shift. The special HMT (Harmonic Mitigating) type Transformer products has been discontinued by Square D / Schneider Electric several years ago. They had specially wound secondaries and different phase shifts you could order. The K-rated Transformers are our only offer now for high harmonic applications.