Video: How is basic programming performed on the ATS22 Soft Starter?
Issue:
How do I perform basic programming on the ATS22?
Product Line:
Altistart 22 Soft Start
Environment:
All models and serial numbers
Resolution:
Basic Programming:
Conf Menu
Uln = line voltage
In= motor rated current (motor FLA)
LAC= Advanced mode to access other menus
Set Menu
t90= Initial voltage
ILt= current limit (max current the motor will be allowed to pull)
ACC= Acceleration time (user preference per application requirements)
DEC= Deceleration time (user preference per application requirements)
tHP= Motor thermal protection (10,20,30) Note: To activate tHP, set ItH to ErUn or On
Pro Menu
ItH= Overload protection (oFF / ErUn / On)
The following video walks the user through basic configuration of the ATS22:
The basic programming parameters to set up an ATS22 Soft Start can also be found in the User Manual.
https://www.se.com/us/en/download/document/BBV51330/
How do I perform basic programming on the ATS22?
Product Line:
Altistart 22 Soft Start
Environment:
All models and serial numbers
Resolution:
Basic Programming:
Conf Menu
Uln = line voltage
In= motor rated current (motor FLA)
LAC= Advanced mode to access other menus
Set Menu
t90= Initial voltage
ILt= current limit (max current the motor will be allowed to pull)
ACC= Acceleration time (user preference per application requirements)
DEC= Deceleration time (user preference per application requirements)
tHP= Motor thermal protection (10,20,30) Note: To activate tHP, set ItH to ErUn or On
Pro Menu
ItH= Overload protection (oFF / ErUn / On)
The following video walks the user through basic configuration of the ATS22:
The basic programming parameters to set up an ATS22 Soft Start can also be found in the User Manual.
https://www.se.com/us/en/download/document/BBV51330/
Gepubliceerd voor: Schneider Electric Netherlands
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.