Onze merken

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Waarmee kunnen wij u vandaag helpen?
What is the level of high voltage, the isolation of XBTHPE was tested ?

Goals and Symptoms

What is the level of high voltage, the isolation of XBTHPE was tested ?

Facts and Changes

high voltage
isolation
XBTHPE
insulation

Causes and Fixes

Here are the levels that the XBTHPE terminals withstand:
Insulation resistance test :
With a voltage of 500V dc, applied between power connections and enclosure ---> Resistance < 10Mohms for new product. Resistance < 1Mohms after heat/humidity test.

Dieletric strength :
With a voltage of 500V ac , applied between each internal isolated cards and then , between all the internal card and the enclosure ---> Leackage current < 5mA.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings