How to use Portmon to Monitor Traffic in Serial Networks

Issue
Serial communications are not functioning on a Modbus daisy chain.

Product Line
Serial Devices

Environment
Windows OS
Portmon 3.x

Resolution

PortMon is a free application that monitors and displays all serial and parallel port activity on the local computer or a remote computer. It intercepts I/O control commands at the driver level and shows detailed information about parameters and data being sent or received.

To monitor traffic in a Modbus daisy chain, the PC running PortMon must be part of the communication (e.g., as a master or slave). PortMon cannot sniff traffic passively on the wire; it only logs what the OS sends/receives through its ports.

How to Run PortMon

  1. How to Run PortMon

    1. Run PORTMON.EXE.
    2. Go to Computer > Connect (choose local or remote).
    3. Under Capture, ensure Capture Events is checked.
    4. Under Capture > Ports, select the port to monitor.
    5. Events for the selected port will appear in the PortMon window.
    6. When done, you can Save the log file for review.

Where to Download:

Portmon can be found on the Windows website by searching Portmon or by following this link: https://learn.microsoft.com/en-us/sysinternals/downloads/portmon.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Algemene handelsvoorwaarden
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings