Onze merken

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Waarmee kunnen wij u vandaag helpen?
Is RE17RMMW product’s output able to drive 26Vdc 20mA load?

The output of RE17RMMW product is an electromechanical relay. This relay is designed to operate a resistive load.  You may operate a small inductive load if needed. Please take note that, the relay contacts lifespan will reduce when we operated an inductive load.

Attached herewith is the life curves specification of the electromechanical relay component. (Refer to attachment)

Schneider Electric Netherlands

bijlage(n)
Output Specification.pdf [47.93 KB]
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings