Waarmee kunnen wij u vandaag helpen?

Video: How do I change the IP address of a Momentum M1E that has all ready been saved to flash?

Issue:

How do I change the IP address of a Momentum M1E that has all ready been saved to flash?

Product Line:

Momentum, PLC, Concept

Resolution:

If an IP address has been saved to the flash memory in the M1E processor then all you have to do is open the Concept project that was downloaded into the M1E and edit the configuration off-line. Change the IP address settings in the Extension or Ethernet I/O scanner pages then connect to the controller with the old IP Download and save the new configuration to flash, go off line and power cycle.

If you do not know the currently saved IP address then you can use Wireshark which is a free downloadable software at www.wireshark.org to find the lost IP address. Once you find the lost IP address then connect with Concept and download and flash the new Concept project as described above.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Algemene handelsvoorwaarden
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings