Waarmee kunnen wij u vandaag helpen?
How to detect a power supply failure on a channel for the 'BMXAMOxxxx' analog output module on a local rack using IODDT
Issue
Show how to detect a power supply failure on a channel for the 'BMXAMOyyyy' analog output module on a local rack using IODDT
Product Line
BMXAMO0410
Environment
Unity, Control Expert
Resolution
The following steps can be used to detect a power supply failure on a channel for the 'BMXAMOyyyy' analog output module
installed on a local rack, with an IODDT variable:
To configure the IODDT:
-Double click on an empty slot in the rack to open the 'New Device' window.
-Select the analog module.
-Click on 'IO datatype topological'.
-Click on OK.
-Double click on the analog module.
-Click on the module name (e.g., BMX AMO 040
-Click on the 'IO object' tab.
-Click on the '%MW' checkbox next to 'Status'.
-Click on 'Update grid with'
-Open the 'Data Editor'.
-Add a variable name.
-Assign the address for the IODDT variable named 'INT_PS_FLT' located at address %MWr.m.c.3.3..
Gepubliceerd voor: Schneider Electric Netherlands
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.