Which cable reference can we use between TM3XTRA1 (TM3 bus extension transmitter module) and TM3XREC1 (extension receiver module)?

The extension receiver module TM3XREC1 can be at maximum distance of 5 meters from the TM3XTRA1.

The Catalog recommend to use the references VDIP1845460xx:

  • VDIP184546005 (0.5 m)
  • VDIP184546010 (1.0 m)
  • VDIP184546020 (2.0 m)
  • VDIP184546030 (3.0 m)
  • VDIP184546050 (5.0 m)

But as these references do not meet the UL requirements, for US market machine installation needs, it’s advised to use 2 other references:

  • 490NTW00002U (2.0 m)
  • 490NTW00005U (5.0 m)

which are UL rated.