Is there an example on how to Sync the time between an HMISTU and M241?
Issue:
When using the HMISTU and M241 PLC, is there a way to read the time information from the M241 PLC and use that to synchronize the HMISTU's internal clock?
Product Line:
Vijeo Designer, SoMachine, Magelis HMI, XBTGT, XBTGK, HMISTO, HMISTU, HMIGTO, HMIGTU, HMIGK
Resolution:
In order to synchronize the HMI time with the M241 time, you must make use of a few libraries in SoMachine.
You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Vijeo Designer.
For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Gepubliceerd voor: Schneider Electric Netherlands
bijlage(n)
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.