Onze merken

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Waarmee kunnen wij u vandaag helpen?
What could cause an OCF Overcurrent Fault on ATV630 or ATV930?
Issue:
Getting a OCF Overcurrent Fault on ATV630 or ATV930.

Product Line:
Altivar AC Drive Process Drive ATV320 ATV71 ATV600 ATV900

Environment:
All

Cause:
Motor pulling higher than nameplate Full Load Amps for an extended period of time

Resolution:
Typically, this can be resolved by adjusting the Motor Control Parameters, and ensuring the motor nameplate information was entered correctly.  Motor Control Parameters vary by application.
If adjusting these parameters does not resolve the issue, you need to determine whether the drive and/or motor is correctly sized to be able to handle the load.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Categorie:
Ontdek meer
Productfamilie
Categorie:
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings