Onze merken

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Waarmee kunnen wij u vandaag helpen?
Do the PowerLogic and ION meters support low voltage DC power supplies?
Issue
Customer would like to determine available DC Low Voltage Supply options for a meter

Product line
PowerLogic Meter
ION Meter

Environment
Power Supply

Cause
Customer wants to determine available DC Low Voltage Supply options for a meter

Resolution
MeterSpecification
ION9000No DC low voltage supply option
ION7550/7650 20-60 V DC
PM8000 series20-60 V DC ±10 %
ION8650/8600Auxiliary DC low voltage supply 80-160 V DC ±20 % only
ION620020-60 V DC
CM4000 seriesNo DC low voltage supply option
PM5000 seriesNo DC low voltage supply option
PM800No DC low voltage supply option
ION7400No DC low voltage supply option
ION770020-60 V DC

Schneider Electric Netherlands

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings