How many oscillograph captures of a failure can be stored on a Sepam 80?

Issue
The user wishes to know how many oscillograph captures of a failure can be stored on a Sepam 80

Product Line
Sepam series 80

Environment
Memory

Resolution
To get the number of oscillograph captures that can be stored in the cartridge, you have to divide the available memory recording capacity, in seconds, by the desired length of each oscillograph capture.

​
MMS020 standard memory cartridge
Total duration of a recording: 1 s to 20 s

Maximum recording capacity
  • 22 s at 50 Hz, 12 samples per period
  • 7 s at 50 Hz, 36 samples per period
  • 18 s at 60 Hz, 12 samples per period
  • 6 s at 60 Hz, 36 samples per period
Examples:
Where the bracket notation
⌊x⌋ represents rounding down to the nearest integer
For a 1 second oscillograph capture length at 60 Hz and 12 samples per period with MMS020 standard memory cartridge: ⌊ (18 s) / (1 s) ⌋= ⌊ 18 ⌋ = 18 captures
For a 5 second oscillograph capture length at 60 Hz and 12 samples per period with MMS020 standard memory cartridge:
⌊ (18 s) / (5 s) ⌋= ⌊ 3.6 ⌋= 3 captures
For a 15 second oscillograph capture length at 60 Hz and 12 samples per period with MMS020 standard memory cartridge: ⌊ (18 s) / (15 s) ⌋= ⌊ 1.2 ⌋= 1 capture

MMR020 extended memory cartridge
Total duration of a recording: 1 s to 32 s

Maximum recording capacity
  • 1 s to 32 s if using an extended cartridge
  • 35 s at 50 Hz, 12 samples per period
  • 11 s at 50 Hz, 36 samples per period
  • 28 s at 60 Hz, 12 samples per period
  • 9 s at 60 Hz, 36 samples per period
Examples:
Where the bracket notation
⌊x⌋ represents rounding down to the nearest integer
For a 1 second oscillograph capture length at 60 Hz and 12 samples per period with MMR020 extended memory cartridge: ⌊ (28 s) / (1 s) ⌋= ⌊ 28 ⌋ = 28 captures
For a 5 second oscillograph capture length at 60 Hz and 12 samples per period with MMS020 extended memory cartridge:
⌊ (28 s) / (5 s) ⌋= ⌊ 5.6 ⌋ = 3 captures
For a 15 second oscillograph capture length at 60 Hz and 12 samples per period with MMS020 extended memory cartridge: ⌊ (28 s) / (15 s) ⌋= ⌊ 1.56 ⌋ = 1 capture

For information on how many event messages of failure can be stored on the Sepam 80, please refer to Sepam 80 event numbers:
(1) How many events of failure can be stored?
(2) How many oscilograph waves of a failure can be stored?

Schneider Electric Netherlands

Ontdek meer

Productfamilie

Ontdek meer

Productfamilie

Hulp nodig?

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.