Onze merken

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Waarmee kunnen wij u vandaag helpen?
What is the MODBUS Register Mapping of SNTP Diagnostics Data for CPUs and communication modules in M580?

SNTP Diagnostic data of 57 words, are available on CPUs and BMENOC0301/11 communication modules using Modbus function code 3 with the unit ID set to 100, offset Modbus Address 1218 and below is the MODBUS Register Mapping:

AddressMS ByteLS ByteCIP TypeComments
1218MSW - MSBMSW - LSBUint32Primary NTP Server IP Address
Offset + 01LSW - MSBLSW - LSB
Offset + 02MSW - MSBMSW - LSBUint32Secondary NTP Server IP Address
Offset + 03LSW - MSBLSW - LSB
Offset + 04UnusedBYTEUint8Polling Period (in seconds)
Offset + 05UnusedBYTEUint8Update CPU with Module Time
Offset + 06MSW - MSBMSW - LSBUint32Time Zone
Offset + 07LSW - MSBLSW - LSB
Offset + 08MSBLSBInt16Time Zone Offset (in minutes)
Offset + 09UnusedBYTEUint8Daylight saving time bias (in minutes)
Offset + 10UnusedLSBUint8Daylight Saving Start Date - Month
Offset + 11UnusedLSBUint8Daylight Saving Start Date - week #, day of week
MS 4-bits: occurrence # (1 = 1st occurrence, 2 = 2nd occurrence…, 5 = fifth or last occurrence)
LS 4-bits: day of the week (0 = Sunday…, 6 = Saturday)
Offset + 12MSW - MSBMSW - LSBUint32Daylight Saving Start Time (seconds elapsed from midnight)
Offset + 13LSW - MSBLSW - LSB
Offset + 14UnusedLSBUint8Daylight Saving End Date - Month
Offset + 15UnusedLSBUint8Daylight Saving End Date - week #, day of week
Offset + 16MSW - MSBMSW - LSBUint32Daylight Saving End Time (seconds elapsed from midnight)
Offset + 17LSW - MSBLSW - LSB
Offset + 18UnusedBYTEUint8SNTP Mode
Offset + 19UnusedBYTEUint8Reserved
Offset + 32UnusedBYTEUint8Reserved
Offset + 33MSW - MSBMSW - LSBUDINTNetwork Time Service Status
Offset + 34LSW - MSBLSW - LSB
Offset + 35MSW - MSBMSW - LSBUDINTLink to NTP Server Status
Offset + 36LSW - MSBLSW - LSB
Offset + 37MSW - MSBMSW - LSBUDINTCurrent NTP Server IP Address
Offset + 38LSW - MSBLSW - LSB
Offset + 39MSW - MSBMSW - LSBUDINTNTP NTP Server Type
Offset + 40LSW - MSBLSW - LSB
Offset + 41MSW - MSBMSW - LSBUDINTNTP Server Time Quality
Offset + 42LSW - MSBLSW - LSB
Offset + 43MSW - MSBMSW - LSBUDINTNumber of NTP Requests Sent
Offset + 44LSW - MSBLSW - LSB
Offset + 45MSW - MSBMSW - LSBUDINTNumber of Communication Errors
Offset + 46LSW - MSBLSW - LSB
Offset + 47MSW - MSBMSW - LSBUDINTNumber of NTP Reponses Received
Offset + 48LSW - MSBLSW - LSB
Offset + 49MSBLSBUINTLast Error
Offset + 50MSW - MSBMSW - LSBUDINTCurrent Time
Offset + 51LSW - MSBLSW - LSB
Offset + 52MSBLSBUINTCurrent Date
Offset + 53MSW - MSBMSW - LSBUDINTDaylight Savings Status
Offset + 54LSW - MSBLSW - LSB
Offset + 55MSW - MSBMSW - LSBDINTTime Since Last Update
Offset + 56LSW - MSBLSW - LSB

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings