Waarmee kunnen wij u vandaag helpen?

How do contacts 95-96 and 97-98 operate on the LTMR product?

Issue:
Contacts 95-96 and 97-98 do not appear to be operating properly.

Product Line:
Tesys T LTMR motor controllers.

Environment:
All models, All serial numbers.

Cause:
Unexpected operation

Resolution:
Contacts 95-96 are labeled as Normally Closed but are open when de-energized.  Contacts 97-98 are labeled as Normally Open but are closed when de-energized.   When power is applied to the LTMR, the unit will perform a self test which usually completes in 7 to 10 seconds, but may take as much as 30.   After the Power On Self Test has completed, if no faults are found, the relay will be energized internally and contact 97-98 will open, 95-96 will close.   This is normal operation.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Algemene handelsvoorwaarden
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings