Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Waarmee kunnen wij u vandaag helpen?
What would cause the ATV320 series Drive to still trip on OBF if the DB resistor has been installed?

Issue:

ATV320 Drive is tripping on OBF after installing the DB resistor.

Product Line:

ATV320...... C version.

Environment:

All

Cause:

DC bus is still over charging on ramp down.

Resolution:

-Check to make sure the Jumper factory jumper is still installed between PO and PA+ ( C suffix version Drives only)

-Check to make sure the DB resistor is wired between PO and PB.

-Power down the drive, let the DC bus discharge then check the DB resistors value across PO and PB. (Drive needs to be powered OFF to do this test)

-Check the programming under FUN, rPt the bRA to make sure its set to NO.

-Verify the correct DB resistor size has been installed.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings