How do I log Time stamping events of the BMXERT1604T module via the OFS server?
Issue:
logging Time stamping events of the BMXERT1604T module via the OFS server
Product Line:
OFS Server, EcoStruxure Control Expert, BMXERT1604T
Resolution:
Below are the steps to configure Control Expert and the OFS server.
1. Ensure that Control Expert "Time Stamping Mode" is set to "System"
2. In this example, I will log channel 0 and 1 discrete value
3. In the OFS configuration tool, I will leave the Timestamp group name to the default as shown. This name we will use for the group name for the testing client.
4. Ensure that the Time Stamped Events service is checked. You can change polling rate for the ERT accordingly. It is left at default
5. Create a directory and then create a text file in that directory. The events will log to this file. In this example, the directory is called EVENT_LOG and the file name is ERT.txt
6. Rick click on the shortcut for the OFS testing client and modify the Target. Add the following at the end of the string
-l C:\EVENT_LOG\ERT.TXT as shown. So the full string should be
"C:\Program Files (x86)\Schneider Electric\OFS\Samples\OFSClient\ofsclient.exe" -l C:\EVENT_LOG\ERT.TXT
7. When creating the group, give it the name ##TSEventsGroup##
8. As you can see, the two variables are updated in the event group.
9. As shown, the events are being logged to the file
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Gepubliceerd voor: Schneider Electric Netherlands

