Ecostruxure Machine Scada Expert - Display trend Date and Time at the cursor position.

Issue:
How can we display the Date and Time at the cursor position on the Trend object?

Product Line:
EcoStruxure Machine SCADA Expert (all versions)

Resolution:
The date and time at the cursor position is not directly available on the trend graphic. In order to display it, some elements must be configured.

1- Create a global "String" tag that will receive the date and time:

Project Explorer - Global tab - right click on "Tag List" to insert a tag.

Insert Tag

In the window, enter the name of the tag and select "String" as the type.

Create the String Tag

2- Double click on the "Trend Control Object" to open the properties window.

Click on the "Axes" button.

Then the "Cursor" button in the new window.

Enter the tag name in the "Value Output" field.

Associate the string tag to the axes cursor value output

3- On the graphic page, add a text object to display the date and time.

Go into the "Draw" menu, select the "Text" tool and add a text field.

Define the properties of text field, then click the "Text data link" button.

Define the Text Data link to display the string tag

In the "Tag/Expression", enter the tag name.

Save the modifications.

Test, the date and time at the cursor position should display.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric Netherlands

bijlage(n)
Test_Trend.zip [304.62 KB]
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings