Power Monitoring Expert Installer Fails at Create Database Folder step due to Access is Denied error

Issue:

PME Installer gives user "access is denied" error at the Create Database Folder step.

Product Line:

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

Power Monitoring Expert Installer

Cause:

PME Folder reverts back to Read-Only even after unselecting the option for the PME Folder properties.

Resolution:

  1. Navigate to the File Explorer
  2. Go to the File path where you have selected the PME folder to be placed during installation.

NOTE: File path should be similar to this example: C:\Program Files (x86) \Schneider Electric

  1. Navigate to the Power Monitoring Expert Folder
  2. Right-click the folder and select Properties
  3. Navigate to the Security Tab
  4. Once in Security select a user from the Groups and User Names option
  5. Select Edit and in the Permissions box select Full Control
  6. Select Apply and OK
  7. Repeat steps 6-9 for all users found in the Groups and User Names section
  8. Once all users have Full Control of the PME folder navigate back to the PME installer
  9. Re-run the failed Created Database Folder step and the installer should finish this step successfully

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Algemene handelsvoorwaarden
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings