Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Waarmee kunnen wij u vandaag helpen?
What is the current consumption (burden) of IRIG-B port in a PM8000, ION7400, or ION9000 meter?

Issue

What is the current consumption (burden) of IRIG-B port in a PM8000, ION7400, or ION9000 meter?

Product Line

PM8000, ION7400, and ION9000 meter

Environment

IRIG-B Port

Resolution

For the ION9000, PM8000 and ION7400 meters, IRIG-B uses the onboard digital inputs. These inputs are an “active impedance” that adjusts to the applied voltage. When the voltage is >=4V it will set the active input impedance to sink about 1-2mA.

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings