Which is the IP rating for reference LV429267 -plug in base, ComPact NSX 100/160/250, front/rear connected, 4 poles ?

Article available in these languages:

  • Frans
  • , Nederlands

- Additional components, shutters for base, are available to ensure IP40 degree of protection. Exposure to energized components are avoided during racking In / Out. It doesn’t allow a probe of 1mm diameter to enter an energized zone.


- Even without use of shutters, we ensure IP2X – Finger proof – So the operator will not be exposed to energized components unless otherwise if they intentionally use a tool / screw driver to access the energized components.


Shutters reference numbers:

LV429271 - NSX100-250

LV432521 - NSX400/630


The plug-in version, provided it is installed respecting the instructions with the required insulation accessories (eg: short terminal shields of the breaker terminals), ensures the following IP protection degree:

- Circuit breaker plugged in = IP4x

- Circuit breaker removed = IP2x

- Circuit breaker removed, base equipped with shutters LV432521 = IP4x.

Schneider Electric Netherlands

Ontdek meer
Product:
Ontdek meer
Product:
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings