Waarmee kunnen wij u vandaag helpen?

How to online Install a Brand-New M580 CPU in a hot standby system

When installing a brand-new CPU during the production operation of the system,

-do not connect the network cable between the master and standby CPUs.

After the CPU and CRA are all fully operational, connect the network cable to construct the ring network.

-Alternatively, in accordance with the operating procedure outlined in the user manual,

you can first download the program to the brand-new CPU independently, then integrate the CPU into the on-site control system.

Control Expert manual capture

Schneider Electric Netherlands

Ontdek meer
Product:
Ontdek meer
Product:
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings