Waarmee kunnen wij u vandaag helpen?

Is It possible to mix standard powered sensors and two-wire sensors in the STBACI1400 analog input STB module?

Issue:

Is It possible to mix standard powered sensors and two-wire sensors on the 4-5-6 inputs of the STBACI1400 analog input STB module ?

Environment:

STBACI1400 analog input STB module

Advantys Configuration Software / EcoStruxure Control Expert

Answer:

It is NOT possible mix standard powered sensors and two-wire sensors on the 4-5-6 inputs of the STBACI1400 because input 6 serves as the "return" or common for inputs 4 and 5.

For powered sensors, connect input 3 or 6 to the sensor, not to the (-) of the power supply.

EXAMPLE:

For Powered sensors:

Capture 1

For 2 wires sensors:

Capture 2

Schneider Electric Netherlands

Ontdek meer
Product:
Ontdek meer
Product:
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings