Waarmee kunnen wij u vandaag helpen?

Troubleshooting DriverPCSService Registration Errors in Geo SCADA Expert

If you encounter the following error when using Geo SCADA Expert (GSE) as an OPC UA server, it points to a registration issue involving the AVEVA Platform Common Services (PCS) framework:

"DriverPCSService failed to register this service with the OCS WCF Proxy"

In order to capture and review these error messages within your system, please gather the Archestra Logger logs by following the steps outlined in this Schneider Electric FAQ Article (FAQ000267704).

While not a guaranteed fix for every environment, one of the primary troubleshooting options to resolve this error is ensuring that the Windows user account running your OPC UA services has been granted membership in the local Windows ASBSolution group.

Troubleshooting Option: Add the User to the ASBSolution Group

Step 1: Add the Account to the ASBSolution Group

  1. Press Win + R, type compmgmt.msc, and press Enter to open Computer Management.

  2. Navigate to System Tools > Local Users and Groups > Groups.

  3. Locate and double-click the ASBSolution group. (Note: If this group is completely missing from the list, your PCS installation may be corrupted or incomplete).

  4. Click Add... and select the Windows user account that requires permissions to connect.

  5. Click OK, then click Apply to save your changes.

addUser

Step 2: Apply the Changes

For the group membership changes to take effect on the system, restart the machine or restart the active PCS and Geo SCADA driver-related background processes.

⚠️ Note: If assigning the user to the ASBSolution group does not resolve the error on your server, the issue may stem from invalid security certificates or a broken AVEVA PCS Framework installation that requires a repair.

Schneider Electric Netherlands

Ontdek meer
Product:
Ontdek meer
Product:
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Algemene handelsvoorwaarden
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings