What are the relays state of ZBRRA receiver when powered off?
1. What you need to know
When a Harmony ZBRRA receiver has no supply voltage, both output relays sit in their de-energized position: the NC contacts 11-12 and 21-22 are closed, and the NO contacts outputs 12-14 and 22-24 are open. If the supply is cut off while an output is ON, the contacts outputs return to this same de-energized state. Output states are not retained through a power loss; transmitter pairing and the configured output mode are maintained.
2. Understanding the ZBRRA output behaviour
The ZBRRA is a programmable receiver in the Harmony XB5R (plastic) and XB4R (metal) wireless and battery less pushbutton range. It converts radio frames from ZBRT* wireless batteryless transmitters into dry contact outputs. Its two outputs are electromechanical changeover relays, so their unpowered position is a mechanical rest position, not a saved state.
3. Contact state according to receiver condition
| Receiver condition | NC contact (11-12 / 21-22) | NO contact (12-14 / 22-24) | Relay state |
|---|---|---|---|
| Not powered (supply off or lost) | Closed | Open | De-energized - default state |
| Powered, no command received | Closed | Open | De-energized |
| Powered, output ON in monostable mode | Open | Closed | Energized while the command is active |
| Powered, output ON in bistable or stop/start mode | Open | Closed | Energized until the next command |
| Supply lost while the output is ON | Closed | Open | De-energized - the ON state is not maintained |
| Supply restored | Closed | Open | De-energized until a new command is received |
4. Related references
| Function | Reference | Description |
|---|---|---|
| Programmable receiver | ZBRRA | 2 changeover relay outputs 3 A, 24-240 V AC/DC, monostable / bistable / stop-start, 6 indicating LEDs |
| Transmitter | ZBRT1 | Wireless and batteryless transmitter, without head |
| Transmitter head, plastic | ZB5RTA2 | ZB5R plastic pushbutton head, black cap, spring return |
| Transmitter head, metal | ZB4RTA2 | ZB4R metal pushbutton head, black cap, spring return |
| Visual feedback | ZBRV1 | Visual feedback module for ZBRT transmitters |
| Antenna | ZBRA1 | Relay antenna to extend radio range |
Download the instruction sheet from the product page on se.com, browse the current wireless offer in DigiCat, or contact Schneider Electric technical support to validate a layout before installation.
Gepubliceerd voor: Schneider Electric Netherlands
Ontdek meer
Product:
Ontdek meer
Product:
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.