Why would a Micrologic trip unit temporarily lose communications after tripping?

Product Line:
Powerpact P and R, Compact NS, and Masterpact NT and NW, Micrologic Trip Unit

Resolution:
The Micrologic trip unit is designed so that when it trips the circuit breaker, it communicates the cause of trip to the breaker communications module (BCM) and then temporarily breaks communications to the BCM. It takes up to three seconds for communication to be restored between the trip unit and the BCM. During this time, if there are any communication requests from the supervisory software, a communication loss might be observed.

After this communication break, the trip unit automatically restores communications to the BCM. See the attached document for the data bulletin regarding this behavior.

Schneider Electric Norway

Vedlegg
ML Trip Unit Comms after trip.pdf [175.02 KB]
Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:

Trenger du hjelp?

Trenger du hjelp?

Produktvelger

Produktvelger

Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.

Be om tilbud

Be om tilbud

Start din salgsforespørsel online, og vi vil kontakte deg.

Hvor kan du handle?

Hvor kan du handle?

Finn din nærmeste Schneider Electric-distributør enkelt.

Hjelpesenter

Hjelpesenter

Finn alle nødvendige supportressurser samlet på ett sted.

  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Schneider Electric Community
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings