Why might an ATV212 Drive always run at the low speed setting and not follow the analog input signal?

Issue:
ATV212 running at low speed and not following the analog input signal

Product Line:
Altivar ATV212

Environment:
All

Cause:
Drive is not following the remote analog signal coming in on VIA or VIB

Resolution:
The low speed setting is parameter LL.

Verify that the VFD is setup to look for the analog input:
DIP switch SW100 position VIA at U (voltage) or I (current), VIB at U (voltage)
Frequency mode select, FMOd:
1 = VIA input
2 = VIB input

Verify the analog input signal by measuring the mA or Vdc on VIA / VIB.  Also check polarity, (+) on VIA / VIB and (- ) on CC.

Logic input R has factory default assignment as preset speed, F112 = 6, Sr1 = 15Hz.  If R is active, the VFD will run at 15Hz or LL (low limit) only. Check / correct the R input status and assignment.  Note that in an S-Flex product, R is a run permissive input, F112 = 1.  If a replacement ATV212 is installed or the VFD was reset to factory defaults, reprogram the VFD per the S-Flex manual.

Verify that the PID parameter, F360, is set correctly:
0 = no PID control
1 = PID per VIA feedback
2 = PID per VIB feedback

Schneider Electric Norway

Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:
  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Schneider Electric Community
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings