Why is the web page not accessible on ATV61/71 drives?
Issue:
Accessing webpage on ATV61 ATV71 VFDs.
Product Line:
Altivar 61 and 71 drives
Environment:
All models and serial numbers with Ethernet IP option card VW3A3316
Cause:
Java 1.8 is not supported or web server services are not activated.
Resolution:
First, verify that web server services are activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.