Merkene våre

Impact-Company-Logo-English Black-01-177x54

Velkommen til nettstedet til Schneider Electric

Velkommen til nettstedet vårt.
		
Hvordan kan vi hjelpe deg i dag?
How is the S-Flex wired to use or not use the Smoke Purge feature?
Issue:
Wiring S-Flex for the Smoke Purge feature.

Product Line:
S-Flex

Environment:
S-Flex with Bypass option

Cause:
Wiring to enable or disable smoke purge

Resolution:
All S-Flex Series E units that have the BYPASS option will also have a SMOKE PURGE feature, although it is disabled.  To enable the smoke purge function, simply remove the jumper from terminals 3-4 and place it on terminals 9-10.  This feature includes a smoke purge relay, SPR, that is activated by applying 120Vac across terminals 17-18.  When activated, SPR contacts will disable the AFC / BYP controls and energize the bypass contactor coil.  The motor will run with full voltage AC power.


Schneider Electric Norway

Vedlegg
ATV212 S Flex Smoke Purge.png [82.17 KB]
Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:

Trenger du hjelp?

  • Produktvelger

    Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.

  • Be om tilbud

    Start din salgsforespørsel online, og vi vil kontakte deg.

  • Hvor kan du handle?

    Finn din nærmeste Schneider Electric-distributør enkelt.

  • Hjelpesenter

    Finn alle nødvendige supportressurser samlet på ett sted.

  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings