Merkene våre

Impact-Company-Logo-English Black-01-177x54

Velkommen til nettstedet til Schneider Electric

Velkommen til nettstedet vårt.
		
Hvordan kan vi hjelpe deg i dag?
How do you set up an external input with an active low to trigger an external fault on an Altivar Process Drive?
Issue:
Can an external input with an active low to be programmed as an external fault on an Altivar Process Drive?

Product Line:
Altivar 930 and Altivar 630 drive

Environment:
All

Cause:
Wants to turn off a digital input and have the drive trigger an external fault.

Resolution:
Programming:
From Complete Settings and press enter
Go to Error/Warning handling and press enter
Select External Error and press enter
Ex error assign enter and choose DI1 thru DI6 Low  (you must scroll all the way down to the bottom of the selection menu.)
set the external fault as DI1 Low

Schneider Electric Norway

Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:

Trenger du hjelp?

  • Produktvelger

    Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.

  • Be om tilbud

    Start din salgsforespørsel online, og vi vil kontakte deg.

  • Hvor kan du handle?

    Finn din nærmeste Schneider Electric-distributør enkelt.

  • Hjelpesenter

    Finn alle nødvendige supportressurser samlet på ett sted.

  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings