Merkene våre

Impact-Company-Logo-English Black-01-177x54

Velkommen til nettstedet til Schneider Electric

Velkommen til nettstedet vårt.
		
Hvordan kan vi hjelpe deg i dag?
How can you connect the remote HMI to the soft starter, ATS48 soft starter if you are using the RJ45 for a remote Ethernet gateway?

Article available in these languages: Spansk

Issue:
Connecting remote HMI to ATS48 while using the RJ45 for a remote Ethernet gateway.

Product Line:
ATV48

Environment:
All

Cause:
RJ45 ports limits when multiple options are needed.

Resolution:
You can only have one thing plugged into the RJ45 port at a time. There is no way to split the port and use both, one for HMI and one for Ethernet gateway.
One option is to use the remote HMI on the RJ45 port, and then use a Tesys T module to monitor motor amps and voltage etc.

Schneider Electric Norway

Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:

Trenger du hjelp?

  • Produktvelger

    Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.

  • Be om tilbud

    Start din salgsforespørsel online, og vi vil kontakte deg.

  • Hvor kan du handle?

    Finn din nærmeste Schneider Electric-distributør enkelt.

  • Hjelpesenter

    Finn alle nødvendige supportressurser samlet på ett sted.

  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings