My Symmetra RM is on battery even though utility power is present.

Issue:
The Symmetra RM shows On Battery even though there is good quality utility power to the UPS and no faults showing.

Product Line:
Symmetra RM 2kVA - 6kVA
SYH2K6RMI, SYH4K6RMI, SYH6K6RMI

Cause:
The SYXRCC card (firmware version 403) is reporting to the Main Intelligence Module that there is an overall negative current on each of the XR frames.

Resolution:
This can temporarily be resolved by disconnecting the XR communications cable and reconnecting it. However to resolve this issue permanently, replace the SYXRCC card (Part number 885-7015B) with another SYXRCC card that has firmware version 404.

Schneider Electric Norway

Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:

Trenger du hjelp?

Trenger du hjelp?

Produktvelger

Produktvelger

Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.

Be om tilbud

Be om tilbud

Start din salgsforespørsel online, og vi vil kontakte deg.

Hvor kan du handle?

Hvor kan du handle?

Finn din nærmeste Schneider Electric-distributør enkelt.

Hjelpesenter

Hjelpesenter

Finn alle nødvendige supportressurser samlet på ett sted.

  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Schneider Electric Community
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings