When programming my ATS48, why can't I find the t90 (initial starting torque) parameter?
Issue:
Can't find the t90 (initial starting torque) parameter, on my ATS48.

Product Line:
Altistart 48

Environment:
All

Cause:
Manual shows t90 in the SET menu, but customer doesn't see it on their ATS48

Resolution:
The t90 parameter does not appear when Torque Control (CLP) is turned off. In the DRC menu make sure your Torque control (CLP) is set to Yes.
Once turned on, the initial starting torque (t90) is configurable between 20% to 100%, depending on what amount of torque is needed to start.

Schneider Electric Norway

Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:

Trenger du hjelp?

  • Produktvelger

    Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.

  • Be om tilbud

    Start din salgsforespørsel online, og vi vil kontakte deg.

  • Hvor kan du handle?

    Finn din nærmeste Schneider Electric-distributør enkelt.

  • Hjelpesenter

    Finn alle nødvendige supportressurser samlet på ett sted.

  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Schneider Electric Community
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings