What would cause an bOF or brake resistor overload fault on the ATV630 and ATV930 Process drives?

Issue:
ATV630 and ATV930 causes with an bOF or brake resistor overload fault.

Product Line:
ATV630 and ATV930 Process drives

Environment:
All

Cause:
Parameter setting of the braking resistor not correct (brtC, brV, brP)

Resolution:
Principle:
The thermal model of the braking resistor has detected and overload.The themal state of the BR can be monitored with the parameter tHb.

Probable cause:
- parameter setting of the braking resistor not correct (brtC, brV, brP)

Remedies:
- check the nominal power of the braking resistor.
- verify the BR parameters brP, brV, brtC
- check with SoMove service section the thermal states TH1R / TH2R / TH3R
- check the thermal state parameter tHb [Braking Resistor monitoring]

Schneider Electric Norway

Finn ut mer
Produktfamilie:
Finn ut mer
Produktfamilie:

Trenger du hjelp?

Trenger du hjelp?

Produktvelger

Produktvelger

Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.

Be om tilbud

Be om tilbud

Start din salgsforespørsel online, og vi vil kontakte deg.

Hvor kan du handle?

Hvor kan du handle?

Finn din nærmeste Schneider Electric-distributør enkelt.

Hjelpesenter

Hjelpesenter

Finn alle nødvendige supportressurser samlet på ett sted.

  • Produktdokumentasjon
  • Nedlasting av programvare
  • Produktvelger
  • Erstatningsprodukter og utskiftning
  • Kundesenter og support
  • Finn kontorene våre
  • Motta et pristilbud
  • Hvor kan du kjøpe produktet?
  • Schneider Electric Community
  • Karriere
  • Vår profil
  • Rapporter et pliktbrudd
  • Tilgjengelighet
  • Presserom
  • Investorer
  • EcoStruxure
  • Jobbsøk
  • Blogg
  • Personvernerklæring
  • Om informasjonskapsler
  • Vilkår for bruk
  • Change your cookie settings